Wire Gauge Calculator

Wire Gauge Calculator from Gizcalc helps you estimate results quickly within the Engineering category.

  • Instant results
  • Charts & tables
  • Save & compare
  • Private – runs in your browser
Recommended Cable Size —

Sample inputs are pre-filled so you can see a result quickly. Results are estimates only and may not be accurate because prices, interest rates, taxes, fees, fuel costs, tariffs, market returns, medical costs, and local rules can change. Please verify current values before making financial, tax, legal, medical, or business decisions.

Formula used

A (mm²) = k × L × I × ρ ÷ V_drop

  • k = 2 for single-phase or DC, √3 for three-phase
  • ρ = resistivity at 70 °C: copper ≈ 0.0206, aluminium ≈ 0.0339 Ω·mm²/m
  • V_drop = supply voltage × allowed drop %

About the Wire Gauge Calculator

What is the Wire Gauge Calculator?

Long cable runs lose voltage. This wire size calculator finds the smallest cross-section that keeps the voltage drop within your limit, then rounds up to the next standard metric size.

It uses conductor resistance at a 70 °C operating temperature and also shows the nearest American Wire Gauge (AWG).

How to use the Wire Gauge Calculator

  1. Supply (sample: Single-phase / DC (2 conductors))
  2. Load Current (A) (sample: 32)
  3. Cable Length, One Way (m) (sample: 25)
  4. Supply Voltage (V) (sample: 230)
  5. Allowed Voltage Drop (%) (sample: 3)
  6. Conductor (sample: Copper)
  7. Press Find Wire Size (results also refresh as you type). The result card shows the Recommended Cable Size, along with Minimum cross-section for the voltage drop, Voltage drop with this size, Nearest AWG and Also check.

Formula used

A (mm²) = k × L × I × ρ ÷ V_drop

  • k = 2 for single-phase or DC, √3 for three-phase
  • ρ = resistivity at 70 °C: copper ≈ 0.0206, aluminium ≈ 0.0339 Ω·mm²/m
  • V_drop = supply voltage × allowed drop %

Electrical work on mains supplies must be done by a licensed electrician, following IS 732 and the CEA safety regulations.

Worked example

These are the sample values already filled in the calculator above, and the result it returns for them:

InputSample value
SupplySingle-phase / DC (2 conductors)
Load Current (A)32
Cable Length, One Way (m)25
Supply Voltage (V)230
Allowed Voltage Drop (%)3
ConductorCopper
ResultValue
Recommended Cable Size6 mm²
Minimum cross-section for the voltage drop4.772 mm²
Voltage drop with this size2.39%
Nearest AWG9
Also checkThe cable's current rating for its installation method (IS 694 / manufacturer tables)

Tips for using the Wire Gauge Calculator

  • Always check the cable's current-carrying capacity as well; the larger of the two sizes applies.
  • Aluminium needs about 1.6 times the cross-section of copper for the same drop.

Frequently asked questions

For a 3% drop on 230 V single-phase, at least 4.8 mm² of copper – use 6 mm².

A common design limit is 3% for lighting and 5% for other circuits.

PVC-insulated cables run up to 70 °C at full load, when resistance is about 20% higher than at 20 °C.