UPS Sizing Calculator

UPS Sizing Calculator from Gizcalc helps you estimate results quickly within the Engineering category.

  • Instant results
  • Charts & tables
  • Save & compare
  • Private – runs in your browser
UPS Rating —

Sample inputs are pre-filled so you can see a result quickly. Results are estimates only and may not be accurate because prices, interest rates, taxes, fees, fuel costs, tariffs, market returns, medical costs, and local rules can change. Please verify current values before making financial, tax, legal, medical, or business decisions.

Formula used

Battery Ah = Load (W) × Backup hours ÷ (Bank voltage × Inverter efficiency × Depth of discharge)

  • UPS VA = load W ÷ power factor × 1.25

About the UPS Sizing Calculator

What is the UPS Sizing Calculator?

This UPS size calculator works out two things: the UPS rating in VA, with a 25% margin over your load, and the battery capacity in ampere-hours needed for the backup time you want.

It then suggests a battery combination for the chosen bank voltage.

How to use the UPS Sizing Calculator

  1. Connected Load (W) (sample: 800)
  2. Load Power Factor (sample: 0.8)
  3. Backup Time Needed (minutes) (sample: 30)
  4. Battery Bank Voltage (sample: 24 V (2 in series))
  5. Usable Depth of Discharge (%) (sample: 80)
  6. Inverter Efficiency (%) (sample: 85)
  7. Press Size UPS and Batteries (results also refresh as you type). The result card shows the UPS Rating, along with Battery capacity needed, Suggested batteries, Energy drawn from batteries and Sizing basis.

Formula used

Battery Ah = Load (W) × Backup hours ÷ (Bank voltage × Inverter efficiency × Depth of discharge)

  • UPS VA = load W ÷ power factor × 1.25

Battery capacity falls in hot rooms and with age; add margin for long backup times.

Worked example

These are the sample values already filled in the calculator above, and the result it returns for them:

InputSample value
Connected Load (W)800
Load Power Factor0.8
Backup Time Needed (minutes)30
Battery Bank Voltage24 V (2 in series)
Usable Depth of Discharge (%)80
Inverter Efficiency (%)85
ResultValue
UPS Rating1,300 VA
Battery capacity needed24.5 Ah
Suggested batteries2 × 12 V 26 Ah
Energy drawn from batteries471 Wh
Sizing basisUPS rated 25% above the load in VA

Tips for using the UPS Sizing Calculator

  • Use sealed maintenance-free (SMF) or lithium batteries indoors.
  • Discharging lead-acid batteries below 50% regularly shortens their life.

Frequently asked questions

About 1,250 VA at 0.8 PF with a 25% margin – a 1.3 kVA or 1.5 kVA UPS.

On a 24 V bank at 85% efficiency and 80% DoD, about 25 Ah – two 12 V 26 Ah batteries.

VA is apparent power; watts are real power. A 1,000 VA UPS typically supplies 600–800 W.