Short Circuit Current Estimator

Short Circuit Current Estimator from Gizcalc helps you estimate results quickly within the Engineering category.

  • Instant results
  • Charts & tables
  • Save & compare
  • Private – runs in your browser
Prospective Short-Circuit Current —

Sample inputs are pre-filled so you can see a result quickly. Results are estimates only and may not be accurate because prices, interest rates, taxes, fees, fuel costs, tariffs, market returns, medical costs, and local rules can change. Please verify current values before making financial, tax, legal, medical, or business decisions.

Formula used

Isc = V ÷ (√3 × Z); Z_transformer = V² ÷ kVA × Z%

  • Z = √(Z_transformer² + R_cable²)
  • At the terminals = Isc = kVA × 1,000 ÷ (√3 × V × Z%)

About the Short Circuit Current Estimator

What is the Short Circuit Current Estimator?

Circuit breakers must be able to interrupt the largest current a fault can cause. This short circuit current estimator works it out from the transformer's kVA rating and percentage impedance, and adds the resistance of the cable to the fault point.

The result guides the breaking capacity (kA rating) of breakers and switchgear.

How to use the Short Circuit Current Estimator

  1. Transformer Rating (kVA) (sample: 500)
  2. Transformer Impedance (%) (sample: 4.5)
  3. Secondary Line Voltage (V) (sample: 415)
  4. Cable Length to the Fault Point (m, 0 at the transformer) (sample: 0)
  5. Cable Size (mm² per phase) (sample: 95 mm²)
  6. Conductor (sample: Copper)
  7. Press Estimate Fault Current (results also refresh as you type). The result card shows the Prospective Short-Circuit Current, along with At the transformer terminals, Transformer impedance, Cable resistance and Breaking capacity needed.

Formula used

Isc = V ÷ (√3 × Z); Z_transformer = V² ÷ kVA × Z%

  • Z = √(Z_transformer² + R_cable²)
  • At the terminals = Isc = kVA × 1,000 ÷ (√3 × V × Z%)

Assumes an infinite upstream fault level, so the estimate errs on the safe (higher) side at the transformer.

Worked example

These are the sample values already filled in the calculator above, and the result it returns for them:

InputSample value
Transformer Rating (kVA)500
Transformer Impedance (%)4.5
Secondary Line Voltage (V)415
Cable Length to the Fault Point (m, 0 at the transformer)0
Cable Size (mm² per phase)95 mm²
ConductorCopper
ResultValue
Prospective Short-Circuit Current15.46 kA
At the transformer terminals15.46 kA
Transformer impedance15.5 mΩ
Cable resistance0 mΩ
Breaking capacity neededChoose breakers rated above 16 kA
AssumptionInfinite upstream fault level – the real value will be slightly lower

Tips for using the Short Circuit Current Estimator

  • Choose breakers with a breaking capacity above the prospective fault current.
  • Fault current falls quickly along small cables – downstream breakers can have lower kA ratings.

Frequently asked questions

At 415 V, about 15.5 kA at the terminals.

The percentage of rated voltage that drives full-load current through a shorted secondary; typically 4–6% for distribution transformers.

The cable adds impedance in series with the transformer.