Generator Sizing Calculator

Generator Sizing Calculator from Gizcalc helps you estimate results quickly within the Engineering category.

  • Instant results
  • Charts & tables
  • Save & compare
  • Private – runs in your browser
Recommended DG Set —

Sample inputs are pre-filled so you can see a result quickly. Results are estimates only and may not be accurate because prices, interest rates, taxes, fees, fuel costs, tariffs, market returns, medical costs, and local rules can change. Please verify current values before making financial, tax, legal, medical, or business decisions.

Formula used

kVA = max(Running kVA × (1 + margin) ÷ 0.8, (Other running kVA + Motor starting kVA) ÷ 1.5)

  • Running kVA = kW ÷ power factor
  • Motor starting kVA = motor running kVA × 6 (DOL), 2.5 (star-delta), 3 (soft starter) or 1.5 (VFD)

About the Generator Sizing Calculator

What is the Generator Sizing Calculator?

An undersized generator trips when motors start; an oversized one wastes fuel. This generator size calculator checks both the continuous running load and the surge when the largest motor starts.

It then picks the next standard DG set rating used in India, such as 62.5, 82.5 or 125 kVA.

How to use the Generator Sizing Calculator

  1. Total Running Load (kW) (sample: 40)
  2. Load Power Factor (sample: 0.8)
  3. Largest Motor Started on the DG (kW, 0 if none) (sample: 7.5)
  4. That Motor's Starting Method (sample: Star-delta (≈2.5×))
  5. Future Expansion Margin (%) (sample: 20)
  6. Press Size the Generator (results also refresh as you type). The result card shows the Recommended DG Set, along with Minimum rating needed, Running load, Needed for continuous running (80% loading + margin) and Needed for motor starting.

Formula used

kVA = max(Running kVA × (1 + margin) ÷ 0.8, (Other running kVA + Motor starting kVA) ÷ 1.5)

  • Running kVA = kW ÷ power factor
  • Motor starting kVA = motor running kVA × 6 (DOL), 2.5 (star-delta), 3 (soft starter) or 1.5 (VFD)

Assumes the set runs at no more than 80% continuous load and tolerates about 150% briefly during motor starting.

Worked example

These are the sample values already filled in the calculator above, and the result it returns for them:

InputSample value
Total Running Load (kW)40
Load Power Factor0.8
Largest Motor Started on the DG (kW, 0 if none)7.5
That Motor's Starting MethodStar-delta (≈2.5×)
Future Expansion Margin (%)20
ResultValue
Recommended DG Set82.5 kVA
Minimum rating needed75 kVA
Running load50 kVA
Needed for continuous running (80% loading + margin)75 kVA
Needed for motor starting43.1 kVA
GovernsRunning load

Tips for using the Generator Sizing Calculator

  • Start the largest motor first, when the set is lightly loaded.
  • Soft starters and VFDs can cut the required DG size substantially.
  • CPCB IV+ emission norms apply to new DG sets up to 800 kW.

Frequently asked questions

At 0.8 PF with a 20% margin, about 75 kVA – an 82.5 kVA set.

Generators are rated in kVA; usable kW = kVA × 0.8 at the standard power factor.

Direct-on-line motors draw about 6 times their running current at start, which can stall an undersized set.