Cooling Capacity Calculator

Cooling Capacity Calculator from Gizcalc helps you estimate results quickly within the Engineering category.

  • Instant results
  • Charts & tables
  • Save & compare
  • Private – runs in your browser
Cooling Capacity —

Sample inputs are pre-filled so you can see a result quickly. Results are estimates only and may not be accurate because prices, interest rates, taxes, fees, fuel costs, tariffs, market returns, medical costs, and local rules can change. Please verify current values before making financial, tax, legal, medical, or business decisions.

Formula used

Q = ṁ × cp × ΔT

  • Air = Q (kW) = 1.2 × 1.005 × airflow (m³/s) × ΔT
  • Water = Q (kW) = flow (kg/s) × 4.186 × ΔT

About the Cooling Capacity Calculator

What is the Cooling Capacity Calculator?

This cooling capacity calculator measures how much heat an AC unit, AHU or chiller is actually removing. Use the air side (airflow and temperature drop across the coil) or the water side (chilled water flow and temperature rise).

It is useful for commissioning and checking whether equipment delivers its rated capacity.

How to use the Cooling Capacity Calculator

  1. Measured On (sample: Air side – airflow and temperature drop)
  2. Airflow (m³/h) (sample: 1,700)
  3. Water Flow (m³/h) (sample: 10)
  4. Temperature Difference (°C) (sample: 10)
  5. Press Calculate Cooling Capacity (results also refresh as you type). The result card shows the Cooling Capacity, along with In tons of refrigeration, In BTU/h and Note.

Formula used

Q = ṁ × cp × ΔT

  • Air = Q (kW) = 1.2 × 1.005 × airflow (m³/s) × ΔT
  • Water = Q (kW) = flow (kg/s) × 4.186 × ΔT

The air-side formula gives sensible cooling; moisture removal adds latent capacity.

Worked example

These are the sample values already filled in the calculator above, and the result it returns for them:

InputSample value
Measured OnAir side – airflow and temperature drop
Airflow (m³/h)1,700
Water Flow (m³/h)10
Temperature Difference (°C)10
ResultValue
Cooling Capacity5.7 kW
In tons of refrigeration1.62 TR
In BTU/h19,432 BTU/h
NoteSensible cooling only; dehumidification adds latent capacity

Tips for using the Cooling Capacity Calculator

  • Chillers are usually designed for a 5 °C rise across the evaporator (7 °C to 12 °C).
  • 1,000 CFM is about 1,700 m³/h.

Frequently asked questions

About 20.9 kW, or 6 TR.

Divide by 3.517.

About 8–12 °C.