About the Cable Sizing Voltage Drop Calculator
What is the Cable Sizing Voltage Drop Calculator?
Already chosen a cable? This voltage drop calculator checks it. Enter the size, length, current, supply and power factor to see the drop in volts and percent, the voltage at the load and the power wasted as heat.
It covers single-phase and three-phase circuits with copper or aluminium conductors.
How to use the Cable Sizing Voltage Drop Calculator
- Supply (sample: Single-phase / DC)
- Cable Size (mm²) (sample: 4 mm²)
- Cable Length, One Way (m) (sample: 30)
- Load Current (A) (sample: 20)
- Supply Voltage (V) (sample: 230)
- Power Factor (sample: 0.9)
- Conductor (sample: Copper)
- Press Check Voltage Drop (results also refresh as you type). The result card shows the Voltage Drop, along with As % of supply, Voltage at the load, Power lost in the cable and Verdict.
Formula used
V_drop = k × I × (ρ × L ÷ A) × PF
- k = 2 for single-phase, √3 for three-phase
- Power loss = n × I² × R, with n = 2 or 3 conductors
Reactance is ignored, which is accurate for cables up to about 35 mm². Electrical work on mains supplies must be done by a licensed electrician, following IS 732 and the CEA safety regulations.
Worked example
These are the sample values already filled in the calculator above, and the result it returns for them:
| Input | Sample value |
|---|---|
| Supply | Single-phase / DC |
| Cable Size (mm²) | 4 mm² |
| Cable Length, One Way (m) | 30 |
| Load Current (A) | 20 |
| Supply Voltage (V) | 230 |
| Power Factor | 0.9 |
| Conductor | Copper |
| Result | Value |
|---|---|
| Voltage Drop | 5.56 V |
| As % of supply | 2.42% |
| Voltage at the load | 224.4 V |
| Power lost in the cable | 123.5 W |
| Verdict | Within 3% – suitable for lighting and all loads |
Tips for using the Cable Sizing Voltage Drop Calculator
- If the drop exceeds 5%, go up one cable size or shorten the run.
- Motors starting on long cables can see dips of 15% or more; check starting current too.